NA2XS(FL)2Y

Application: 

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high durability of laminated polyethylen sheat permits strong mechanical stress during installation or operation. Longitudinally and radially watertight avoids water propagation inside the cable.

Conductor material: Aluminium
Conductor construction: Class 2
Insulation: XLPE DIX 8
Sheathing material: PE DMP 2
Bonded sheath: Yes
Transverse water-tight: Yes
Longitudinally water-tight: Yes
Color of outer sheath: Black
Meter mark: Yes
Flame retardant: No
UV-resistant: Yes
Maximum temperature at conductor: 90 °C
Maximum operating temperature, fixed: 70 °C
Temperature, moved/during installation: -20 / +70 °C
Bending radius, fixed installation: 15 x Da
Partial discharge: 2 pC
Voltage levels: NA2XS(FL)2Y 6/10 kV NA2XS(FL)2Y 12/20 kV NA2XS(FL)2Y 18/30 kV
Nominal voltage Uo: 6 kV 12 kV 18 kV
Nominal voltage U: 10 kV 20 kV 30 kV
Maximum permitted operating
voltage in 3-phase systems:
12 kV 24 kV 36 kV
Test voltage: 21 kV 42 kV 63 kV