Proizvodi
Tehnički predlog
NA2XS2Y
Application:
For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. For installation in cable ducts and indoors must be considered that the PE sheath is halogen-free, but not flame retardant according to DIN VDE 0482-332-1.
| Conductor material: | Aluminium | ||
| Conductor construction: | Class 2 | ||
| Insulation: | XLPE DIX 8 | ||
| Sheathing material: | Polyethylene DMP2 | ||
| Colour of outer sheath: | Black | ||
| Flame retardant: | No | ||
| Maximum temperature at conductor: | 90 °C | ||
| Maximum operating temperature, fixed: | 70 °C | ||
| Temperature, moved/during installation: | -20 / +70 °C | ||
| Bending radius, fixed installation: | 15 x Da | ||
| Partial discharge: | 2 pC | ||
| Voltage levels: | NA2XS2Y 6/10 kV | NA2XS2Y 12/20 kV | NA2XS2Y 18/30 kV |
| Nominal voltage Uo: | 6 kV | 12 kV | 18 kV |
| Nominal voltage U: | 10 kV | 20 kV | 30 kV |
| Maximum permitted operating voltage in 3-phase systems: |
12 kV | 24 kV | 36 kV |
| Test voltage: | 21 kV | 42 kV | 63 kV |