Proizvodi
Tehnički predlog
LiHCH FE180/PH90
Application:
Indoor instrumentation and control cabling, for electrically noisy environments, fire alarm systems in office buildings.
| Conductors: | Stranded copper conductors per IEC 60228 | |
| Insulation: | Cross-linked ceramic forming polymer compound | |
| Core: | Layout in concentric layers | |
| Core wrapping: | Polyester tape + fiberglass tape | |
| Screen: | Tinned copper braiding (min. 85% coverage) | |
| Outer jacket: | HFFR per EN 50290-2-27, Color: orange | |
| Insulation dielectric strength: | 2000 VAC(50 Hz) / 1 minute | |
| Insulation resistance: | 20 MΩ.km | |
| Voltage rating: | 300 V | |
| Bending radius: | > 7.5 x cable diameter | |
| Operation temperature range: | -40 ºC to +90ºC | |
| Single cable flame retardance: | IEC 60332-1 | |
| Bundled cables flame retardance: | IEC 60332-3-24 | |
| Smoke emission: | IEC 61034-2 | |
| Halogen gas content: | IEC 60754-1 | |
| Corrosive gas emission: | IEC 60754-2 | |
| Circuit integrity: | FE 180 per IEC 60331-23 | |
| Circuit integrity under shock: | PH90 per EN 50200 | |