Application:
Low-smoke, zero-halogen flame retardant power cable. For fixed indoor and outdoor installation as well as in concrete, but not for direct burial in ground or application in water.
| Conductor material: | Bare copper | |
| Conductor construction: | Class 1, from 25 mm2 class 2 | |
| Insulation: | XLPE 2XI1 | |
| Sheathing material: | FRNC-compound HM4 | |
| Flame retardant: | VDE 0482-266-2-4/IEC 60332-3-24 (Kat. C) | |
| Smoke density: | DIN EN 61034/IEC 61034 | |
| Halogen free: | DIN EN 50267/IEC 60754 | |
| Maximum temperature at conductor: | 90 °C | |
| Maximum operating temperature, fixed: | -30 / +70 °C | |
| Temperature, moved/during installation: | -5 / +70 °C | |
| Bending radius, fixed installation: | 15 x DA | |
| Cable type: | N2XH-J | N2XH-O |
| Nominal voltage Uo: | 600 V | 600 V |
| Nominal voltage U: | 1 kV | 1 kV |
| Maximum permitted operating voltage in 3-phase systems: |
1,2 kV | 1,2 kV |
| Test voltage: | 4 kV | 4 kV |
| Core identification: | colors acc. VDE 0293 (HD 308) | colors acc. VDE 0293 (HD 308) |