Proizvodi
Tehnički predlog
NHXMH
Application:
Low-smoke zero-halogen flame retardant building wire for installation on and under plaster, in cable ducts and conduits. For indoor use only.
| Conductor material: | Bare copper | |
| Insulation: | XLPE 2XI1 | |
| Sheathing material: | FRNC-compound HM2 | |
| Flame retardant: | VDE 0482-266-2-4/IEC 60332-3-24 (Kat. C) | |
| Smoke density: | DIN EN 61034/IEC 61034 | |
| Halogen free: | DIN EN 50267/IEC 60754 | |
| Maximum temperature at conductor: | 70 °C | |
| Maximum operating temperature, fixed: | 70 °C | |
| Cable type: | NHXMH-J | NHXMH-O |
| Nominal voltage Uo: | 300 V | 300 V |
| Nominal voltage U: | 500 V | 500 V |
| Test voltage: | 2 kV | 2 kV |
| Core identification: | colors acc. VDE 0293 (HD 308) | colors acc. VDE 0293 (HD 308) |
