PP 41 / CYAbY (-F)

Application: 

Power cable for static application, mostly in ground, also in water, within facilities, in cable canals, in concrete. Used for power supply to power stations, transformer stations, industrial plants, metropolitan networks and other electric plants. Applied in conditions requiring protection against heavier mechanical damages, but where cables are not exposed to heavier tensile strain. The cables must be protected against: corozive, chemicals, chemical solvents and solar radiation.

Conductor material:  Bare copper
Conductor construction: Class 1 – from 25 mm2 class 2
Armor: Blank or zinc-plated coldrolledtape,                              
minimum thickness 0,2-0,5mm
Inner sheath: PVC DMV 17
Insulation: PVC DIV 10
Sheathing material: PVC DMV 17
Color of outer sheath: Gray as standard or black by order
Flame retardant:
SR EN 332-1-2, SR EN 50266-4-2
Maximum operating temperature, fixed: 70 °C
Minimum temperature, moved/during installation: -5 °C
Short-circuit temperature: Max. 160 °C
Nominal voltage Uo: 600 V
Nominal voltage U: 1 kV
Test voltage AC/DC: 3,5 kV/8,4 kV max. 5 min.
Bending radius at installation: Min. 12 x Da
Tensile strain during installation: Max. 50 N/mm2