Proizvodi
Tehnički predlog
PP42 / NYCWY
Application:
For fixed installation in buildings, in free air, in ground for direct burial and in water as it is the flame retardant according to IEC60332-1. Cable includes UV protection.
| Conductor material: | Bare copper |
| Conductor construction: | Class 1, from 25 mm2 class 2 |
| Insulation: | PVC DIV 4 |
| Concentric conductor: | Cu |
| Sheathing material: | PVC DMV 5 |
| Color of outer sheath: | Black |
| Meter mark: | Yes |
| Flame retardant: | VDE 0482-332-1-2/IEC 60332-1 |
| Uv-resistant: | Yes |
| Maximum temperature at conductor: | 70 °C |
| Maximum operating temperature, fixed: | 70 °C |
| Temperature, moved/during installation: | -5 / +70 °C |
| Nominal voltage Uo: | 600 V |
| Nominal voltage U: | 1 kV |
| Maximum permitted operating voltage in 3-phase systems: |
1,2 kV |
| Test voltage: | 4 kV |
| Core identification: | Colors acc. VDE 0293 (HD308) |