XHE-49 A / NA2XS(F)2Y

Application: 

For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Conductor material:  Aluminuium
Conductor construction: stranded, class 2
Insulation: XLPE DIX 8
Sheathing material: polyethylene DMP2
Longitudinally water-tight: Yes
Colour of outer sheath: Black
Meter mark: Yes
Flame retardant: No
Maximum temperature at conductor: 90 °C
Maximum operating temperature, fixed: 70 °C
Temperature, moved/during installation: -20 / +70 °C
Bending radius, fixed installation: 15 x Da
Partial discharge: 2 pC
Voltage levels: NA2XS(F)2Y 6/10 kV NA2XS(F)2Y 12/20 kV NA2XS(F)2Y 18/30 kV
Nominal voltage Uo: 6 kV 12 kV 18 kV
Nominal voltage U: 10 kV 20 kV 30 kV
Maximum permitted operating
voltage in 3-phase systems:
12 kV 24 kV 36 kV
Test voltage: 21 kV 42 kV 63 kV