Proizvodi
Tehnički predlog
XHE-49 / N2XS(F)2Y
Application:
For installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.
| Conductor material: | Bare copper | ||
| Conductor construction: | Stranded, class 2 | ||
| Insulation: | XLPE DIX 8 | ||
| Sheathing material: | Polyethylene DMP2 | ||
| Longitudinally water-tight: | Yes | ||
| Colour of outer sheath: | Black | ||
| Meter mark: | Yes | ||
| Flame retardant: | No | ||
| UV-resistant: | Yes | ||
| Maximum temperature at conductor: | 90 °C | ||
| Maximum operating temperature, fixed: | 70 °C | ||
| Temperature, moved/during installation: | -20 / +70 °C | ||
| Bending radius, fixed installation: | 15 x Da | ||
| Partial discharge: | 2 pC | ||
| Voltage levels: | N2XS(F)2Y 6/10 kV | N2XS(F)2Y 12/20 kV | N2XS(F)2Y 18/30 kV |
| Nominal voltage Uo: | 6 kV | 12 kV | 18 kV |
| Nominal voltage U: | 10 kV | 20 kV | 30 kV |
| Maximum permitted operating voltage in 3-phase systems: |
12 kV | 24 kV | 36 kV |
| Test voltage: | 21 kV | 42 kV | 63 kV |